The switches RELF and RELF ex are:
- air insulated (AIS)
- in metal casing
- completely metal clad
- of type retractable
- equipped with a single main bar
- available for nominal voltages up to 36 kV
- designed exclusively for indoor use
Main electrical data:
RELF:
- Nominal voltages: 12 / 17.5 / 24 / 36(40.5)* kV
- Rated current (main and input bars): 630 A to 4000 A
- Power frequency withstand voltage: 28 / 38 / 50 / 95 kV
- Atmospheric impulse withstand voltage: 75 / 95 / 125 / 190 kV
- Rated frequency: 50 Hz
- Permissible short-circuit current (3 s): up to 40 kA
- Permissible peak current: up to 100 kA
- Internal arc resistance: up to 31.5 kA/1 s or up to 40 kA/0.5 s
- Protection degree: up to IP4X (IP3X for 4000 A current)
- Cabinet dimensions:
- Height: 2200 – 2250 mm
- Width: 600 – 1000 mm
- Depth: 1250 / 1575 / 1675 mm
RELF ex:
- Nominal voltages: 12 / 17.5 kV
- Rated current: 630 – 2500 A
- Power frequency withstand voltage: 28/38 kV
- Atmospheric impulse withstand voltage: 75 / 95 kV
- Rated frequency: 50 Hz
- Permissible short-circuit current (3 s): up to 25 kA
- Permissible peak current: up to 63 kA
- Internal arc resistance: up to 25 kA/1 s
- Protection degree: up to IP4X
- Cabinet dimensions:
- Height: 2250 mm
- Width: 650 / 800 / 1000 mm
- Depth: 1375 / 1388 mm
Compliance with standards:
- (PN-EN) IEC 62271-200
- (PN-EN) IEC 62271-1
Terms of use:
- Ambient temperature:
- short-term maximum: +40°C
- daily average maximum: +35°C
- annual average: +20°C
- long-term minimum: -5°C
- Relative air humidity:
- maximum daily average: 95%
- maximum monthly average: 90%
- Water vapor pressure:
- maximum daily average: 2.2 kPa
- monthly average maximum: 1.8 kPa
- Atmosphere at the installation site:
- without significant contamination with salt, vapors, dust, smoke, flammable or corrosive gases
- without ice, frost or condensation
- Installation altitude: up to 1000 m above sea level
- Vibrations: negligible (without significant external influences or earthquakes)