Medium voltage switch type RXD is:
- air-insulated
- metal-clad
- available in retractable or fixed version (depending on equipment)
- equipped with a unique bar system
- intended for nominal voltages of 12 kV or 36 kV
- designed for use inside
This switch offers:
- maximum performance encased in an air-insulated metal housing
- safe and efficient operation at voltages up to 36 kV
- ideal for use in transformer stations and power plants
- high configurability and possibility of expansion through additional modules
- retractable version that can include contactor, circuit breaker, voltage transformers with fuses
Increased safety is ensured by:
- retractable module maneuverable with the housing door closed
- internal spring-resistant housing
- door locks
- uninterrupted operation even during maintenance
Electrical data:
RXD 12 kV:
- Nominal voltage: 12 kV
- Rated continuous current through main busbars and inputs: 630 – 1250 A
- Power frequency withstand voltage: 28 kV
- Atmospheric impulse withstand voltage: 75 kV
- Rated frequency: 50 Hz
- Rated permissible short-circuit current (1 s): up to 25 kA
- Permissible peak current: up to 63 kA
- Internal arc resistance: up to 25 kA/1 s
- Protection degree: up to IP4X
- Cabinet dimensions:
- height: 2250 mm
- width: 600 / 700 / 750 / 900 mm
- depth: 1188 mm
RXD 36 kV:
- Nominal voltage: 36 kV
- Rated continuous current: 630 A
- Power frequency withstand voltage: 85 kV (5 min) / 95 kV (1 min) / 120 kV (5 min)
- Atmospheric impulse withstand voltage: 190 / 220 kV
- Rated frequency: 50 Hz
- Rated permissible short-circuit current (1 s): up to 25 kA
- Permissible peak current: up to 63 kA
- Internal arc resistance: up to 20 kA/1 s
- Protection degree: up to IP4X
- Cabinet dimensions:
- height: 2600 mm
- width: 1600 / 2000 mm
- depth: 1888 mm
Compliance with standards:
- (PN-EN) IEC 62271-200
- (PN-EN) IEC 62271-1
Terms of use:
- Ambient temperature:
- short-term maximum: +40°C
- daily average maximum: +35°C
- long-term minimum: -5°C
- Relative air humidity:
- maximum daily average: 95%
- maximum monthly average: 90%
- Water vapor pressure:
- maximum daily average: 2.2 kPa
- monthly average maximum: 1.8 kPa
- Atmosphere at the installation site:
- without significant contamination with salt, vapors, dust, smoke, flammable or corrosive gases
- no ice, frost or condensation formation
- Installation altitude:
- up to 1000 m above sea level
- Vibrations:
- vibrations caused by external factors or earthquakes – negligible